Kortslutningsberäkningar och kontroll av selektivitet för del av mellanspänningsnätet vid AkzoNobel i Stenungsund
University West, Department of Engineering Science, Division of Computer, Electrical and Surveying Engineering.
University West, Department of Engineering Science, Division of Computer, Electrical and Surveying Engineering.
2016 (Swedish)Independent thesis Basic level (university diploma), 10 credits / 15 HE creditsStudent thesisAlternative title
Short circuit calculation and selectivity analysis for part of medium voltage network at AkzoNobel in Stenungsund (English)
Abstract [sv]

Examensarbetet har utförts åt ÅF Industry Stenungsund, på uppdrag av AkzoNobel. Uppdraget består i att utföra kortslutningsberäkningar i programvaran Vision samt upprätta en selektivplan. Vid kortslutningsberäkning är det de maximala samt de minimala värdena på kortslutningseffekt och kortslutningsström som beräknas. Då det är kortslutningsströmmen, som skydden ska bryta innan den gör åverkan på anläggningen. Kontroll av selektivitet har utförts från överliggande nät på 10,8 kV ner till ett lågspänningsställverk på 0,525 kV i anläggningen.

För att kunna genomföra detta uppdrag måste först all data på kablar, transformatorer, skenor och skydd samlas in. Ett enlinjeschema över AkzoNobels anläggning ritas sedan i programvaran med parametrar från uppdragsgivaren. I enlinjeschemat utförs kortslutningsberäkningar i alla låg- och mellanspänningsställverk. Selektivplanen utförs genom att skydden läggs in i enlinjeschemat samt att inställningarna skrivs in i Vision. När alla skydd är inlagda i programvaran kan dessa markeras, och på så sätt visas, enskilt eller tillsammans med flera skydd, i ett ström-tid-diagram. Bedömningen av selektivitet är att anläggningen inte påverkas av att lågspänningsskyddet i LSP-10 inte är selektivt i alla fellägen med närmaste ovanliggandeskydd SPAC 331C SPCJ 4D44 i underliggande ställverk D.

Abstract [en]

This thesis has been developed for ÅF Industry, Stenungsund, on behalf of AkzoNobel. The assignment consists of performing short circuit calculations in the program software Vision, in addition establishing a selective plan. When doing short circuit calculations it is the maximum and the minimum values on short circuit power and short circuit current that is calculated, since it is the short circuit current that the protection will break before it does damage on the installation. The selectivity analysis has been done from an overhead network on 10, 8 kV down to a low voltage signal box on 0,525 kV in the plant.

To be able to complete this mission, data on cables, transformers, rails and protection is gathered. A single line diagram over AkzoNobels plant is later drawn into the software with parameters given by our client. Short circuit calculations are made in the single line diagram in all low and middle voltage switchgear. The selective plan is conducted by placing the protection in the single line diagram, in addition to having the settings added to the Vision. When all protections are installed in the software, they will be marked and in that way, individually or together, be shown in a current-time-diagram. The assessment of the selectivity is that the plant does not get effected by low voltage protection in LSP-10 that is not selective in all fault modes with the closest overhead protection SPAC 331C SPCJ 4D44 in underlying switchgear D.

Place, publisher, year, edition, pages
2016. , 14 p.
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
URN: urn:nbn:se:hv:diva-9801Local ID: EXH300OAI: oai:DiVA.org:hv-9801DiVA: diva2:955332
Subject / course
Electrotechnology
Educational program
Elkraft
Supervisors
Examiners
Available from: 2016-08-26 Created: 2016-08-25 Last updated: 2016-08-26Bibliographically approved

Open Access in DiVA

No full text

By organisation
Division of Computer, Electrical and Surveying Engineering
Electrical Engineering, Electronic Engineering, Information Engineering

Search outside of DiVA

GoogleGoogle Scholar

Total: 32 hits
ReferencesLink to record
Permanent link

Direct link